PRODUCTS

Main Sandwich panels Firewall System 200.1 and 230.1

Firewall System 200.1 and 230.1

Ruukki Firewall System
2

Ruukki Firewall prevents fire from spreading to neighboring rooms or nearby buildings.

 

Ruukki Firewall is based on Ruukki sandwich panels with mineral wool filling. Additional fire protection is provided by sealing all joints with mineral wool inserts, using sealants with fire-resistant seals, as well as a reinforced fastening system.

 

Ruukki Firewall is suitable for use in houses with frames made of steel, concrete or wood.

 

The Ruukki Firewall system is available in thicknesses of 200 and 230 mm and provides fire resistance under mechanical impact of EI-M 90 for a span of up to 7.5 m and EI-M 120 for a span of up to 6 m, which significantly exceeds the regulatory requirements for the 1st and the 2nd type firewall.

 

Firewall system typeFire resistance
Ruukki Firewall systemEI-M 90 & EI-M 120
Requirements of DBN 1.1-7:2016
1st type firewall systemEI 45
2nd type firewall systemEI 15

 

Technical documentation

  • Properties
  • Technical documentation
Properties
Geometric properties
Model nameRuukki Firewall 200.1 & 230.1
Module width, mm1,200
Minimum length, mm2,000
Maximum length, mm7,500
External facing thickness, mm0.70
Internal facing thickness, mm0.70


Thermal properties
Thickness, mm200230
Weight, kg/m236.140.2
U-value 25 °С, W/m2∙K0.220.19
Sound insulation, Rw, Db:3131
Fire reaction classA2-s1,d0A2-s1,d0


Fire characteristics
Fire resistance under mechanical impact200230
EI-M 907.57.5
EI-M 1206.06.0

 